Technical Data
4.14 Monitoring Functions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
359
4.14
Monitoring Functions
Measured Values
Trip Circuit Monitoring
Current sum
I
F
= |
I
L1
+
I
L2
+
I
L3
+ k
I
·
I
E
| >
SUM.I Threshold ·
I
N
+ SUM.
I
FACTOR ·
Σ
|
I
|
- SUM.
I
Limit
for
I
N
= 1 A
0.10 A to 2.00 A
Increment 0.01 A
for
I
N
= 5 A
0.50 A to 10.00 A
Increment 0.01 A
- SUM.
I
FACTOR
0.00 to 0.95
Increment 0.01
Voltage sum
U
F
= | U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
| > 25 V
Current Symmetry
|
I
min
|/|
I
max
| < BAL.FACTOR.
I
as long as
I
max
/
I
N
> BAL.
I
LIMIT/
I
N
- BAL.FACTOR.
I
0.10 to 0.95
Increment 0.01
- BAL.
I
LIMIT
for
I
N
= 1 A
0.10 A to 1.00 A
Increment 0.01 A
for
I
N
= 5 A
0.50 A to 5.00 A
Increment 0.01 A
- T BAL.
I
LIMIT
5 s to 100 s
Increments 1 s
Broken wire
monitoring of current transformer circuits on current step change
without voltage step change
Voltage balance
| U
min
|/| U
max
| < BAL.FACTOR.U
as long as | U
max
| > BAL.ULIMIT
- BAL.FACTOR.U
0.58 to 0.95
Increment 0.01
- BAL.ULIMIT
10 V to 100 V
Increment 1 V
- T BAL.ULIMIT
5 s to 100 s
Increments 1 s
Voltage phase sequence
U
L1
leads U
L2
leads U
L3
as long as | U
L1
|, | U
L2
| , | U
L3
| > 40 V/v3
Asymmetrical measuring voltage failure
(Fuse Failure Monitor)
3 · U
0
> FFM U> OR 3 · U
2
> FFM U>
AND simultaneously
3 ·
I
0
< FFM
I
< AND 3 ·
I
2
< FFM
I
<
- FFM U>
10 V to 100 V
Increments 1 V
- FFM
I
<
for
I
N
= 1 A
0.10 A to 1.00 A
Increment 0.01 A
for
I
N
= 5 A
0.50 A to 5.00 A
Increment 0.01 A
Three-phase measuring voltage failure
(Fuse Failure Monitor)
all U
Ph-E
< FFM UMEAS <
AND simultaneously
all
Δ
I
Ph
< FFM
I
delta
- FFM UMEAS <
2 V to 100 V
Increments 1 V
- FFM
I
delta
for
I
N
= 1 A
0.05 A to 1.00 A
Increment 0.01 A
for
I
N
= 5 A
0.25 A to 5.00 A
Increment 0.01 A
- T V SUPERVISION (waiting time for additional
measured voltage failure monitoring)
0.00 s to 30.00 s
Increments 0.01 s
- T mcb
0 ms to 30 ms
Increments 1 ms
Number of supervised trip circuits
1 to 3
Operation of each trip circuit
With 1 binary input or with 2 binary inputs
Pickup and dropout time
Approx. 1 to 2 s
Settable delay time for operation with 1 binary input
1 s to 30 s
Increments 1 s
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...