Functions
2.17 Additional Functions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
251
Table 2-11
Operational measured values of the local device
1)
according to address 1104
2)
according to address 1103
3)
considering factor 221 I4/Iph CT
Measured Values
Primary
Second-
ary
% Referred to
I
L1
;
I
L2
;
I
L3
Phase currents
A
A
Nominal operational current
3
I
0
Earth current
A
A
Nominal operational current
ϕ
(
I
L1
-I
L2
),
ϕ
(
I
L2
-
I
L3
),
ϕ
(
I
L3
-
I
L1
)
Phase angle of the phase currents
towards each other
°
–
–
I
1
,
I
2
Positive and negative sequence cur-
rents
A
A
Nominal operational current
I
Y
Transformer starpoint current
A
A
Nominal operational current
U
L1-L2
, U
L2-L3
, U
L3-L1
Phase-to-phase voltages
kV
V
Nominal operational voltage
U
L1-E
, U
L2-E
, U
L3-E
Phase-earth voltage
kV
V
Rated operational voltage /
√
3U
0
Displacement Voltage
kV
V
Rated operational voltage /
√
ϕ
(U
L1
-U
L2
),
ϕ
(U
L2
-U
L3
),
ϕ
(U
L3
-U
L1
)
Phase angle of the phase voltages
towards each other
°
–
–
ϕ
(U
L1
-
I
L1
),
ϕ
(U
L2
-
I
L2
),
ϕ
(U
L3
-
I
L3
)
Phase angle of the phase voltages
towards the phase currents
°
–
–
U
1
, U
2
Positive and negative sequence com-
ponent of the voltages
kV
V
Rated operational voltage /
√
U
X
, U
EN
Voltage at measuring input U
4
–
V
–
U
1compound
Positive sequence component of volt-
ages at the remote end (if compound-
ing is active in voltage protection)
kV
V
Operational rated voltage /
√
S, P, Q
Apparent, active and reactive power
MVA,
MW,
MVAR
–
√
3·U
N
·
I
N
Nominal operational
quantities
cos
ϕ
Power factor
(abs)
(abs)
–
f
Frequency (constellation frequency)
Hz
Hz
Nominal Frequency
Θ
L1
/
Θ
TRIP
,
Θ
L2
/
Θ
TRIP
,
Θ
L3
/
Θ
TRIP
Thermal value of each phase,
referred to the tripping value
%
–
Trip overtemperature
Θ
/
Θ
TRIP
Resulting thermal value,
referred to the tripping value, calculat-
ed according to the set method
%
–
Trip overtemperature
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...