Appendix
A.7 Settings
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
396
3932
T-PoleDiscrep.
Breaker Failure
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay with pole discrepancy
4001
FCT TripSuperv.
TripCirc.Superv
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
TripCirc.Superv
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
TripCirc.Superv
1 .. 30 sec
2 sec
Delay Time for alarm
4101
REF PROT.
REF
OFF
ON
OFF
Restricted Earth Fault Protection
4111
I-REF>
REF
1A
0.05 .. 2.00 A
0.15 A
Pick up value I REF>
5A
0.25 .. 10.00 A
0.75 A
4112A
T I-REF>
REF
0.00 .. 60.00 sec;
∞
0.00 sec
T I-REF> Time Delay
4113A
SLOPE
REF
0.00 .. 0.95
0.00
Slope of Charac. I-REF> = f(I-
SUM)
4201
Ther. OVERLOAD
Therm. Overload
OFF
ON
Alarm Only
OFF
Thermal overload protection
4202
K-FACTOR
Therm. Overload
0.10 .. 4.00
1.10
K-Factor
4203
TIME CONSTANT
Therm. Overload
1.0 .. 999.9 min
100.0 min
Time Constant
4204
Θ
ALARM
Therm. Overload
50 .. 100 %
90 %
Thermal Alarm Stage
4205
I ALARM
Therm. Overload
1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm Setpoint
5A
0.50 .. 20.00 A
5.00 A
4206
CALC. METHOD
Therm. Overload
Θ
max
Average
Θ
Θ
from Imax
Θ
max
Method of Acquiring Tempera-
ture
4501
STATE PROT I 1
Prot. Interface
ON
OFF
ON
State of protection interface 1
4502
CONNEC. 1 OVER
Prot. Interface
F.optic direct
Com conv 64 kB
Com conv 128 kB
Com conv 512 kB
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct
Connection 1 over
4505A
PROT 1 T-DELAY
Prot. Interface
0.1 .. 30.0 ms
30.0 ms
Prot 1: Maximal permissible
delay time
4506A
PROT 1 UNSYM.
Prot. Interface
0.000 .. 3.000 ms
0.100 ms
Prot 1: Diff. in send and receive
time
4509
T-DATA DISTURB
Prot. Interface
0.05 .. 2.00 sec
0.10 sec
Time delay for data disturbance
alarm
4510
T-DATAFAIL
Prot. Interface
0.0 .. 60.0 sec
6.0 sec
Time del for transmission failure
alarm
4511
PI1 SYNCMODE
Prot. Interface
TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS
PI1 Synchronizationmode
4512
Td ResetRemote
Prot. Interface
0.00 .. 300.00 sec;
∞
0.00 sec
Remote signal RESET DELAY
for comm.fail
4513A
PROT1 max ERROR
Prot. Interface
0.5 .. 20.0 %
1.0 %
Prot 1: Maximal permissible error
rate
4515A
PI1 BLOCK UNSYM
Prot. Interface
YES
NO
YES
Prot.1: Block. due to unsym.
delay time
4701
ID OF RELAY 1
Diff.-Topo
1 .. 65534
1
Identification number of relay 1
4702
ID OF RELAY 2
Diff.-Topo
1 .. 65534
2
Identification number of relay 2
4710
LOCAL RELAY
Diff.-Topo
relay 1
relay 2
relay 1
Local relay is
4801
GPS-SYNC.
Prot. Interface
ON
OFF
OFF
GPS synchronization
4803A
TD GPS FAILD
Prot. Interface
0.5 .. 60.0 sec
2.1 sec
Delay time for local GPS-pulse
loss
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...