Functions
2.10 Automatic Reclosure Function (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
141
2.10.2
Setting Notes
General
If no reclosure is required on the feeder to which the 7SD610 differential protection is applied (e.g. for cables,
transformers) the auto reclose function must be removed during configuration of the device (address
133
, see
Section 2.1.1.2). The auto reclose function is then fully disabled, i.e. the automatic reclosure is not processed
in the 7SD610. No signals regarding the auto reclose function are generated, and the binary inputs for the auto
reclose function are ignored. All parameters for setting the auto reclose function are inaccessible and of no sig-
nificance.
But if the internal automatic reclosure function is to be used, the type of reclosure must be selected during the
configuration of the device functions (see Section 2.1.1.2) in address
133
Auto Reclose
and in address
134
the
AR control mode
.
Up to 8 reclosure attempts are allowed with the integrated automatic reclosure function in the 7SD610.
Whereas the settings in address
3401
to
3441
are common to all reclosure cycles, the individual settings of
the cycles are made from address
3450
onwards. It is possible to set different individual parameters for the
first four reclose cycles. From the fifth cycle on the parameters for the fourth cycle apply.
The automatic reclosing function can be turned
ON
or
OFF
under address
3401
AUTO RECLOSE
.
A prerequisite for automatic reclosure taking place after a trip due to a short-circuit is that the circuit breaker is
ready for at least one OPEN-CLOSE-OPEN cycle at the time the automatic reclosure circuit is started, i.e. at
the time of the first trip command. The readiness of the circuit breaker is signalled to the device via the binary
input
„>CB1 Ready“
(No. 371). If no such signal is available, leave the setting under address
3402
CB?
1.TRIP
=
NO
because no automatic reclosure would be possible at all otherwise. If circuit breaker interrogation
is possible, you should set
CB? 1.TRIP
=
YES
.
Furthermore, the circuit breaker ready state can also be interrogated prior to every reclosure. This is set when
setting the individual reclose cycles (see below).
To check that the ready status of the circuit breaker is regained during the dead times, you can set a circuit
breaker ready monitoring time under address
3409
CB TIME OUT
. The time is set slightly longer than the re-
covery time of the circuit breaker after an OPEN-CLOSE-OPEN cycle. If the circuit breaker is not ready again
by the time this timer expires, no reclosure takes place and the automatic reclosure function is blocked dynam-
ically.
Waiting for the circuit breaker to be ready can lead to an increase of the dead times. To avoid uncontrolled pro-
longation, it is possible to set a maximum prolongation of the dead time in this case in address
3411
T-DEAD
EXT.
. This prolongation is unlimited if the setting
∞
is applied. This parameter can only be altered with DIGSI
under
Additional Settings
. Remember that longer dead times are only permissible after three-pole tripping
when no stability problems occur.
T-RECLAIM
(address
3403
) is the time after which the fault is considered eliminated following successful re-
closure. If a protection function provokes a new trip before this time has elapsed, the next reclosing cycle is
started in case of multiple reclosure. If no further reclosing attempt is allowed, the last reclosure will be consid-
ered failed in the event of a new trip. The reclaim time must therefore be longer than the longest response time
of a protection function which can start the automatic reclosure function. When operating the AR in ADT mode,
it is possible to deactivate the reclaim time by setting it to 0 s.
A few seconds are generally sufficient. In areas with frequent thunderstorms or storms, a shorter blocking time
may be necessary to avoid feeder lockout due to sequential lightning strikes or cable flashovers.
A longer reclaim time should be chosen where circuit breaker supervision is not possible (see above) during
multiple reclosures, e.g. because of missing auxiliary contacts and information on the circuit breaker ready
status. In this case, the reclaim time should be longer than the time required for the circuit breaker mechanism
to be ready.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...