![Siemens SIPROTEC 7SD610 Скачать руководство пользователя страница 342](http://html.mh-extra.com/html/siemens/siprotec-7sd610/siprotec-7sd610_manual_382669342.webp)
Technical Data
4.6 Transmission of Binary Information (optional)
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
342
4.6
Transmission of Binary Information (optional)
Remote commands
Remote signals
Number of possible remote commands
4
The operating times depend on the communication speed.
The following data require a transmission rate of 512 kBit/s.
The operating times refer to the entire signal path from entry via binary inputs until output of commands via output relays.
Operating times, total approx.
minimum
13 ms
typical
17 ms
Dropout times, total approx.
typical
24 ms
Number of possible remote signals
24
The operating times depend on the communication speed.
The following data require a transmission rate of 512 kBit/s.
The operating times refer to the entire signal path from entry via binary inputs until output of commands via output relays.
Operating times, total approx.
minimum
14 ms
typical
21 ms
Dropout times, total approx.
typical
29 ms
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...