Appendix
A.7 Settings
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
395
3749A
U2>(>) RESET
Voltage Prot.
0.30 .. 0.99
0.98
U2>(>) Reset ratio
3751
Uph-e<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode Uph-e under-
voltage prot.
3752
Uph-e<
Voltage Prot.
1.0 .. 100.0 V; 0
30.0 V
Uph-e< Pickup
3753
T Uph-e<
Voltage Prot.
0.00 .. 100.00 sec;
∞
2.00 sec
T Uph-e< Time Delay
3754
Uph-e<<
Voltage Prot.
1.0 .. 100.0 V; 0
10.0 V
Uph-e<< Pickup
3755
T Uph-e<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T Uph-e<< Time Delay
3758
CURR.SUP. Uphe<
Voltage Prot.
ON
OFF
ON
Current supervision (Uph-e)
3759A
Uph-e<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
Uph-e<(<) Reset ratio
3761
Uph-ph<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode Uph-ph under-
voltage prot.
3762
Uph-ph<
Voltage Prot.
1.0 .. 175.0 V; 0
50.0 V
Uph-ph< Pickup
3763
T Uph-ph<
Voltage Prot.
0.00 .. 100.00 sec;
∞
2.00 sec
T Uph-ph< Time Delay
3764
Uph-ph<<
Voltage Prot.
1.0 .. 175.0 V; 0
17.0 V
Uph-ph<< Pickup
3765
T Uphph<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T Uph-ph<< Time Delay
3768
CURR.SUP.Uphph<
Voltage Prot.
ON
OFF
ON
Current supervision (Uph-ph)
3769A
Uphph<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
Uph-ph<(<) Reset ratio
3771
U1<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode U1 undervolt-
age prot.
3772
U1<
Voltage Prot.
1.0 .. 100.0 V; 0
30.0 V
U1< Pickup
3773
T U1<
Voltage Prot.
0.00 .. 100.00 sec;
∞
2.00 sec
T U1< Time Delay
3774
U1<<
Voltage Prot.
1.0 .. 100.0 V; 0
10.0 V
U1<< Pickup
3775
T U1<<
Voltage Prot.
0.00 .. 100.00 sec;
∞
1.00 sec
T U1<< Time Delay
3778
CURR.SUP.U1<
Voltage Prot.
ON
OFF
ON
Current supervision (U1)
3779A
U1<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
U1<(<) Reset ratio
3901
FCT BreakerFail
Breaker Failure
ON
OFF
ON
Breaker Failure Protection
3902
I> BF
Breaker Failure
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3903
1p-RETRIP (T1)
Breaker Failure
NO
YES
YES
1pole retrip with stage T1 (local
trip)
3904
T1-1pole
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 1pole start (local
trip)
3905
T1-3pole
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 3pole start (local
trip)
3906
T2
Breaker Failure
0.00 .. 30.00 sec;
∞
0.15 sec
T2, Delay of 2nd stage (busbar
trip)
3907
T3-BkrDefective
Breaker Failure
0.00 .. 30.00 sec;
∞
0.00 sec
T3, Delay for start with defective
bkr.
3908
Trip BkrDefect.
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
Trip output selection with defec-
tive bkr
3909
Chk BRK CONTACT
Breaker Failure
NO
YES
YES
Check Breaker contacts
3912
3I0> BF
Breaker Failure
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold 3I0>
5A
0.25 .. 100.00 A
0.50 A
3913
T2StartCriteria
Breaker Failure
With exp. of T1
Parallel withT1
Parallel withT1
T2 Start Criteria
3921
End Flt. stage
Breaker Failure
ON
OFF
OFF
End fault protection
3922
T-EndFault
Breaker Failure
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay of end fault protection
3931
PoleDiscrepancy
Breaker Failure
ON
OFF
OFF
Pole Discrepancy supervision
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...