Functions
2.1 General
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
37
Current transformer 10P10; 30 VA
→
n = 10; P
N
= 30 VA
Current transformer 10P20; 20 VA
→
n = 20; P
N
= 20 VA
The operational accuracy limit factor n' is derived from these rated data and the actual secondary burden P':
With
n' =
operational accuracy limit factor (effective overcurrent factor)
n =
rated accuracy limit factor of the current transformers (distinctive number behind P)
P
N
=
rated burden of the current transformers [VA] at rated current
P
i
=
internal burden of the current transformers [VA] at rated current
P' =
actually connected burden (d secondary lines) [VA] at rated current
Usually, the internal burden of the current transformers is stated in the test report. If it is unknown, it can be
roughly calculated from the DC resistance R
i
of the secondary winding.
P
i
≈
R
i
·
I
N
2
The ratio between operational accuracy limit factor and rated accuracy limit factor n'/n is set at address
251
K_ALF/K_ALF_N
.
The CT error at rated current, plus a safety margin, is set at address
253
E% ALF/ALF_N
. It is equal to the
„current measuring deviation for primary nominal current intensity F1“ according to VDE 0414 / Part 1 or IEC
60044. It is
– 3 % for a 5P transformer,
– 5 % for a 10P transformer.
The CT error at rated accuracy limit factor, plus a safety margin, is set at address
254
E% K_ALF_N
. It is
derived from the number preceding the P of the transformer data.
Table 2-1 illustrates some usual protective current transformer types with their characteristic data and the rec-
ommended settings.
Table 2-1
Recommended settings for current transformer data
1)
If n'/n
≤
1.50, setting = calculated ratio; if n'/n > 1.50, setting = 1.50
CT class
Standard
Error at rated current
Error at rated
accuracy limit
factor
Recommended settings
Transforma-
tion ratio
Angle
Address 251
Address 253
Address 254
5P
IEC 60044-1
1,0 %
±
60 min
≤
5 %
≤
3,0 %
10,0 %
10P
3,0 %
—
≤
10 %
≤
5,0 %
15,0 %
TPX
IEC 60044-1
0,5 %
±
30 min
ε
≤
10 %
≤
1,0 %
15,0 %
TPY
1,0 %
±
30 min
ε
≤
10 %
≤
3,0 %
15,0 %
TPZ
1,0 %
±
180 min
±
18 min
ε
≤
10 %
(only
I
∼
)
≤
6,0 %
20,0 %
PX
IEC 60044-1
BS: Class X
≤
3,0 %
10,0 %
C100
to
C800
ANSI
≤
5,0 %
15,0 %
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...