Functions
2.9 Backup Time Overcurrent Protection
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
103
Figure 2-39
Logic diagram of the
I
>> stage
1
)
Output indications associated with the pickup signals are listed in Table 2-3
2
)
Output indications associated with the trip signals are listed in Table 2-4
Definite time overcurrent stage
I
>
The logic of the overcurrent stages
I
> is structured identically to the
I
>> stages. In all references,
Iph>>
must
merely be replaced by
Iph>
or
3I0>> PICKUP
by
3I0>
. The parameter
2624
I> Telep/BI
is set to
NO
by
default. In all other respects, figure 2-39 applies.