Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
306
WEB-Monitor
Topology and statistics of the protection data interfaces can be graphically displayed on the screen using the
WEB Monitor. This requires a personal computer with web browser. Figure 3-21 shows the general information
of the communication topology.
Figure 3-21
Communication topology – Limited representation
The „Additional Information“ button extends the representation by the following information:
The timing master is indicated by a clock icon in the communication topology display.
In the event of an incorrect parameterisation or faulty wiring, the indications „Communication topology not com-
plete“ (topol complete OFF), „Communication topology invalid“ and „Protection topology invalid“ are displayed
in a red bar.
The display of the circuit breaker positions is integrated into the topology display. Closed circuit breakers are
displayed in green, opened circuit breakers are displayed in red and circuit breakers in an undefined state are
displayed in grey.
An LED is used to select whether the communication topology or the protection topology is to be displayed for
the participating device. The display of the connections changes correspondingly.
To get an overview of the quality of the individual communication paths, a connection status is displayed for
each connection. The statuses can be „OK“, „asynchronous connection“ and „unknown status“ annehmen.
The status is displayed directly in the communication path display, i.e. in the display of the arrows symbolising
the connection. The colour of the connection indicates its status, a legend at the lower screen edge explains
its colour coding. If a connection fails completely, the connection is no longer displayed.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...