Functions
2.13 Circuit Breaker Failure Protection
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
193
The delay time
T-PoleDiscrep.
(address
3932
) indicates how long a circuit breaker pole discrepancy con-
dition of the feeder circuit breaker, i.e. only one or two poles open, may be present before the pole discrepancy
supervision issues a 3-pole trip command. This time must be clearly longer than the duration of a 1-pole auto-
matic reclose cycle. The time should be less than the permissible duration of an unbalanced load condition
which is caused by the unsymmetrical position of the circuit breaker poles. Conventional values are 2 s to 5 s.
2.13.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
3901
FCT BreakerFail
ON
OFF
ON
Breaker Failure Protection
3902
I> BF
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3903
1p-RETRIP (T1)
NO
YES
YES
1pole retrip with stage T1
(local trip)
3904
T1-1pole
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 1pole start
(local trip)
3905
T1-3pole
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 3pole start
(local trip)
3906
T2
0.00 .. 30.00 sec;
∞
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
3907
T3-BkrDefective
0.00 .. 30.00 sec;
∞
0.00 sec
T3, Delay for start with de-
fective bkr.
3908
Trip BkrDefect.
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
Trip output selection with
defective bkr
3909
Chk BRK CONTACT
NO
YES
YES
Check Breaker contacts
3912
3I0> BF
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold 3I0>
5A
0.25 .. 100.00 A
0.50 A
3913
T2StartCriteria
With exp. of T1
Parallel withT1
Parallel withT1
T2 Start Criteria
3921
End Flt. stage
ON
OFF
OFF
End fault protection
3922
T-EndFault
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay of end fault pro-
tection
3931
PoleDiscrepancy
ON
OFF
OFF
Pole Discrepancy supervi-
sion
3932
T-PoleDiscrep.
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay with pole dis-
crepancy
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...