Functions
2.16 Function Control and Circuit Breaker Test
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
234
Conditions which cause reclosure interlocking and control commands which have to be interlocked can be set
individually. The two inputs and the output can be wired via the correspondingly allocated binary inputs and
outputs or be linked via user-defined logic functions (CFC).
If, for example, each trip by the protection function has to cause a closing lock-out, then combine the tripping
command
„Relay TRIP“
(No. 511) with the binary input
„>Lockout SET“
. If automatic reclosure is used,
only the final trip of the protection function should activate reclosing lock-out. Please bear in mind that the
message
„Definitive TRIP“
(no. 536) applies only for 500 ms. Then combine the output alarm
„Definitive TRIP“
(No. 536) with the interlocking input
„>Lockout SET“
so that the interlocking is not
activated when an automatic reclosure is still expected.
In the simplest case, you can route the output alarm
„LOCKOUT“
(No. 530) to the same output that trips the
cirbuit breaker without creating additional links. Then the tripping command is maintained until the interlock is
reset via the reset input. This requires the close coil at the circuit breaker to be blocked as usual for as long as
a tripping command is maintained.
The output indication
„LOCKOUT“
can also be applied to interlock certain closing commands (externally or via
CFC), e.g. by combining the output alarm with the binary input
„>Blk Man. Close“
(no. 357) or by connect-
ing the inverted alarm with the bay interlocking of the feeder.
The reset input
„>Lockout RESET“
(no. 386) resets the interlocking state. This input is initiated by an external
device which is protected against unauthorized or unintentional operation. The interlocking state can also be
controlled by internal sources using CFC, e.g. a function key, operation of the device or using DIGSI on a PC.
For each case please ensure that the corresponding logic operations, security measures, etc. are taken into
account when routing the binary inputs and outputs and may have to be considered when creating the user-
defined logic functions. See also the SIPROTEC 4 System Description.
Breaker Tripping Alarm Suppression
On feeders without automatic reclosure, every trip command by a protection function is final. But when using
automatic reclosure, it is desired that the operation detector of the circuit breaker (fleeting contact at the break-
er) should only generate an alarm if the trip of the breaker is final (Figure 2-107).
To accomplish this, the signal from the circuit breaker can be routed via an output contact of the 7SD610 (output
alarm
„CB Alarm Supp“
, No. 563) that is configured accordingly. In the idle state and when the device is
turned off, this contact is closed. This requires that a normally closed contact is allocated. Which contact is to
be allocated depends on the device version. See also the general views in the Appendix.
Prior to a trip command with the internal automatic reclosure in the ready state, the contact opens so that the
tripping of the circuit breaker is not passed on. This is only the case if the device is equipped with internal au-
tomatic reclosure and if the latter was taken into consideration when configuring the protection functions (ad-
dress
133
).
Also when closing the breaker via the binary input
„>Manual Close“
(No 356) or via the integrated automatic
reclosure the contact is interrupted so that the breaker alarm is inhibited.
Further optional closing commands which are not sent via the device are not taken into consideration. Closing
commands for control can be linked to the alarm suppression via the user-defined logic functions (CFC).
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...