Appendix
A.7 Settings
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
389
1210
I-DIFF>
Diff. Prot
1A
0.10 .. 20.00 A
0.30 A
I-DIFF>: Pickup value
5A
0.50 .. 100.00 A
1.50 A
1213
I-DIF>SWITCH ON
Diff. Prot
1A
0.10 .. 20.00 A
0.30 A
I-DIFF>: Value under switch on
condition
5A
0.50 .. 100.00 A
1.50 A
1217A
T-DELAY I-DIFF>
Diff. Prot
0.00 .. 60.00 sec;
∞
0.00 sec
I-DIFF>: Trip time delay
1218
T3I0 1PHAS
Diff. Prot
0.00 .. 0.50 sec;
∞
0.04 sec
Delay 1ph-faults (comp/isol. star-
point)
1219A
I> RELEASE DIFF
Diff. Prot
1A
0.10 .. 20.00 A; 0
0.00 A
Min. local current to release
DIFF-Trip
5A
0.50 .. 100.00 A; 0
0.00 A
1233
I-DIFF>>
Diff. Prot
1A
0.8 .. 100.0 A;
∞
1.2 A
I-DIFF>>: Pickup value
5A
4.0 .. 500.0 A;
∞
6.0 A
1235
I-DIF>>SWITCHON
Diff. Prot
1A
0.8 .. 100.0 A;
∞
1.2 A
I-DIFF>>: Value under switch on
cond.
5A
4.0 .. 500.0 A;
∞
6.0 A
1301
I-TRIP SEND
Intertrip
YES
NO
NO
State of transmit. the intertrip
command
1302
I-TRIP RECEIVE
Intertrip
Alarm only
Trip
Trip
Reaction if intertrip command is
receiv.
1303
T-ITRIP BI
Intertrip
0.00 .. 30.00 sec
0.02 sec
Delay for intertrip via binary input
1304
T-ITRIP PROL BI
Intertrip
0.00 .. 30.00 sec
0.00 sec
Prolongation for intertrip via
bin.input
1401
HSD
HighSpeedDIS
ON
OFF
OFF
High Speed Distance Protection
1402
HSD ZHSD
HighSpeedDIS
1A
0.050 .. 600.000
Ω
2.000
Ω
High Speed Distance ZHSD
5A
0.010 .. 120.000
Ω
0.400
Ω
1407
BL.ZHSD.DIFF.A
HighSpeedDIS
YES
NO
NO
High Speed Distance blocked if
Diff.A
2201
FCT Direct Trip
DTT Direct Trip
ON
OFF
OFF
Direct Transfer Trip (DTT)
2202
Trip Time DELAY
DTT Direct Trip
0.00 .. 30.00 sec;
∞
0.01 sec
Trip Time Delay
2301
INRUSH REST.
Diff. Prot
OFF
ON
OFF
Inrush Restraint
2302
2nd HARMONIC
Diff. Prot
10 .. 45 %
15 %
2nd. harmonic in % of fundamen-
tal
2303
CROSS BLOCK
Diff. Prot
NO
YES
NO
Cross Block
2305
MAX INRUSH PEAK
Diff. Prot
1A
1.1 .. 25.0 A
15.0 A
Maximum inrush-peak value
5A
5.5 .. 125.0 A
75.0 A
2310
CROSSB 2HM
Diff. Prot
0.00 .. 60.00 sec;
∞
0.00 sec
Time for Crossblock with 2nd
harmonic
2401
FCT HS/SOTF-O/C
SOTF Overcurr.
ON
OFF
ON
Inst. High Speed/SOTF-O/C is
2404
I>>>
SOTF Overcurr.
1A
0.10 .. 15.00 A;
∞
1.50 A
I>>> Pickup
5A
0.50 .. 75.00 A;
∞
7.50 A
2405A
I>>>>
SOTF Overcurr.
1A
1.00 .. 25.00 A;
∞
∞
A
I>>>> Pickup
5A
5.00 .. 125.00 A;
∞
∞
A
2406
CBaux for I>>>
SOTF Overcurr.
local only
local and rem.
local and rem.
CB-aux check for activation of
I>>>
2601
Operating Mode
Back-Up O/C
ON
Only Emer. prot
OFF
ON
Operating mode
2602
SOTF Time DELAY
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
Trip time delay after SOTF
2603A
Direct. 3I0
Back-Up O/C
U0/I0 or U2/I0
with U0/I0
with U2/I2
U0/I0 or U2/I0
Measurement of direction for 3I0
2610
Iph>>
Back-Up O/C
1A
0.05 .. 50.00 A;
∞
2.00 A
Iph>> Pickup
5A
0.25 .. 250.00 A;
∞
10.00 A
2611
T Iph>>
Back-Up O/C
0.00 .. 30.00 sec;
∞
0.30 sec
T Iph>> Time delay
2612
3I0>> PICKUP
Back-Up O/C
1A
0.05 .. 25.00 A;
∞
0.50 A
3I0>> Pickup
5A
0.25 .. 125.00 A;
∞
2.50 A
2613
T 3I0>>
Back-Up O/C
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0>> Time delay
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...