Functions
2.16 Function Control and Circuit Breaker Test
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
239
2.16.3.3 Setting Notes
Fault Messages
Pickup of a new protection function generally turns off any previously set displays, so that only the latest fault
is displayed at any one time. It can be selected whether the stored LED displays and the spontaneous indica-
tions on the display appear upon renewed pickup, or only after a renewed trip signal is issued. In order to enter
the desired type of display, select the submenu General Device Settings in the SETTINGS menu. At address
610
FltDisp.LED/LCD
the two alternatives
Target on PU
and
Target on TRIP
(„No trip - no flag“) are
offered.
After startup of the device featuring a 4-line display, default measured values are displayed. Use the arrow keys
on the device front to select different measured value views to be used as the so-called default display. The
start page of the default display, which will open after each startup of the device, can be selected via parameter
640
Start image DD
. The available representation types for the measured value are listed in the Appendix.
2.16.3.4 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
2.16.3.5 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
610
FltDisp.LED/LCD
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
625A
T MIN LED HOLD
0 .. 60 min;
∞
0 min
Minimum hold time of lachted
LEDs
640
Start image DD
image 1
image 2
image 3
image 4
image 5
image 6
image 1
Start image Default Display
No.
Information
Type of In-
formation
Comments
-
Test mode
IntSP
Test mode
-
DataStop
IntSP
Stop data transmission
-
UnlockDT
IntSP
Unlock data transmission via BI
-
Reset LED
IntSP
Reset LED
-
SynchClock
IntSP_Ev
Clock Synchronization
-
>Light on
SP
>Back Light on
-
HWTestMod
IntSP
Hardware Test Mode
-
Distur.CFC
OUT
Disturbance CFC
-
Brk OPENED
IntSP
Breaker OPENED
-
FdrEARTHED
IntSP
Feeder EARTHED
3
>Time Synch
SP
>Synchronize Internal Real Time Clock
5
>Reset LED
SP
>Reset LED
11
>Annunc. 1
SP
>User defined annunciation 1
12
>Annunc. 2
SP
>User defined annunciation 2
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...