Appendix
A.7 Settings
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
390
2614
I>> Telep/BI
Back-Up O/C
NO
YES
YES
Instantaneous trip via Tele-
prot./BI
2615
I>> SOTF
Back-Up O/C
NO
YES
NO
Instantaneous trip after Switch-
OnToFault
2620
Iph>
Back-Up O/C
1A
0.05 .. 50.00 A;
∞
1.50 A
Iph> Pickup
5A
0.25 .. 250.00 A;
∞
7.50 A
2621
T Iph>
Back-Up O/C
0.00 .. 30.00 sec;
∞
0.50 sec
T Iph> Time delay
2622
3I0>
Back-Up O/C
1A
0.05 .. 25.00 A;
∞
0.20 A
3I0> Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2623
T 3I0>
Back-Up O/C
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0> Time delay
2624
I> Telep/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
2625
I> SOTF
Back-Up O/C
NO
YES
NO
Instantaneous trip after Switch-
OnToFault
2630
Iph> STUB
Back-Up O/C
1A
0.05 .. 50.00 A;
∞
1.50 A
Iph> STUB Pickup
5A
0.25 .. 250.00 A;
∞
7.50 A
2631
T Iph STUB
Back-Up O/C
0.00 .. 30.00 sec;
∞
0.30 sec
T Iph STUB Time delay
2632
3I0> STUB
Back-Up O/C
1A
0.05 .. 25.00 A;
∞
0.20 A
3I0> STUB Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2633
T 3I0 STUB
Back-Up O/C
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0 STUB Time delay
2634
I-STUB Telep/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
2635
I-STUB SOTF
Back-Up O/C
NO
YES
NO
Instantaneous trip after Switch-
OnToFault
2640
Ip>
Back-Up O/C
1A
0.10 .. 4.00 A;
∞
∞
A
Ip> Pickup
5A
0.50 .. 20.00 A;
∞
∞
A
2642
T Ip Time Dial
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
T Ip Time Dial
2643
Time Dial TD Ip
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
Time Dial TD Ip
2646
T Ip Add
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
T Ip Additional Time Delay
2650
3I0p PICKUP
Back-Up O/C
1A
0.05 .. 4.00 A;
∞
∞
A
3I0p Pickup
5A
0.25 .. 20.00 A;
∞
∞
A
2652
T 3I0p TimeDial
Back-Up O/C
0.05 .. 3.00 sec;
∞
0.50 sec
T 3I0p Time Dial
2653
TimeDial TD3I0p
Back-Up O/C
0.50 .. 15.00 ;
∞
5.00
Time Dial TD 3I0p
2656
T 3I0p Add
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
T 3I0p Additional Time Delay
2660
IEC Curve
Back-Up O/C
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2661
ANSI Curve
Back-Up O/C
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2670
I(3I0)p Tele/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
2671
I(3I0)p SOTF
Back-Up O/C
NO
YES
NO
Instantaneous trip after Switch-
OnToFault
2680
Direction Iph>
Back-Up O/C
Non-Directional
Forward
Reverse
Non-Directional
Direction of stage Iph> Dir.
2681
Iph> Dir.
Back-Up O/C
1A
0.05 .. 50.00 A;
∞
1.50 A
Iph> directional Pickup
5A
0.25 .. 250.00 A;
∞
7.50 A
2682
T Iph> Dir.
Back-Up O/C
0.00 .. 30.00 sec;
∞
0.50 sec
T Iph> Dir. Time delay
2683
Direction 3I0>
Back-Up O/C
Non-Directional
Forward
Reverse
Non-Directional
Direction of stage 3I0> Dir.
2684
3I0> Dir.
Back-Up O/C
1A
0.05 .. 25.00 A;
∞
0.20 A
3I0> directional Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2685
T 3I0> Dir.
Back-Up O/C
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0> Dir. Time delay
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...