Technical data
14.3 Technical data of optional modules
SIPART PS2 with PROFIBUS communication
250
Operating Instructions, 09/2007, A5E00127926-07
Alarm unit
Without explosion
protection
(also EEx d)
With EEx ia/ib explosion
protection
With EEx n explosion
protection
•
Galvanically connected with the
standard controller
Signal status 0
Dry contact, open
Dry contact, open
Dry contact, open
Signal status 1
Dry contact, closed
Dry contact, closed
Dry contact, closed
Contact load
3 V, 5 μA
3 V, 5 μA
3 V, 5 μA
•
Galvanically isolated from the
standard controller
Signal status 0
≤ 4.5 V or open
≤ 4.5 V or open
≤ 4.5 V or open
Signal status 1
≥ 13 V
≥ 13 V
≥ 13 V
Internal resistance
> 25 kΩ
> 25 kΩ
> 25 kΩ
Static destruction limit
± 35 V
-
-
Internal inductance and capacitance -
Negligible
-
Connection to circuits
-
Intrinsically safe U
i
≤ 25.2 V
U
i
≤ 25.2 V DC
Electrical isolation
The three outputs, the BE2 input and the standard controller are galvanically
isolated from each other.
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
SIA unit
(not for the EEx d version)
Without explosion
protection
(also EEx d)
With EEx ia/ib explosion
protection
With EEx n explosion
protection
6DR4004-8G (without
explosion protection)
6DR4004-6G (with
explosion protection)
6DR4004-6G (with
explosion protection)
Limit indicator with slotted initiators
and fault message output
2-wire connection
2-wire connection
2-wire connection
Explosion protection
Without
II 2 G EEx ia/ib IIC T6
II 3 G EEx nA L [L] IIC T6
Connection
2-wire technique as per EN60947-5-6 (NAMUR), for switching amplifier to be
connected downstream
2 slotted initiators
Type SJ2-SN
Type SJ2-SN
Type SJ2-SN
Function
NC, normally closed
NC, normally closed
NC, normally closed
Connection to circuits with
Nominal voltage 8 V;
current consumption:
≥ 3 mA (limit not
responded),
≤ 1 mA (limit responded)
Intrinsically safe switching
amplifier EN60947-5-6
U
i
≤ 15.5 V DC
I
k
≤ 25 mA
P
i
≤ 64 mW
U
i
≤ 15.5 V DC
P
i
≤ 64 mW
Internal capacitance
-
≤ 41 nF
-
Internal inductance
-
< 100 mH
-
Electrical isolation
The three outputs are galvanically isolated from the standard controller
Test voltage
840 V DC, 1 s
840 V DC, 1 s
840 V DC, 1 s
Fault message output
See alarm unit
See alarm unit
See alarm unit
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......