Alarm, fault and system messages
12.4 Fault correction
SIPART PS2 with PROFIBUS communication
236
Operating Instructions, 09/2007, A5E00127926-07
12.4
Fault correction
12.4.1
Fault identification
Diagnostics guide
Fault
See fault table
In which mode does a fault occur?
•
Initialization
1
•
Manual and automatic modes
2
3
4
5
In which environment and under which boundary conditions does a fault occur?
•
Wet environment (e.g. strong rain or constant condensation)
2
•
Vibrating (oscillating) control valves
2
5
•
Impact or shock loads (e.g. vapor shocks or breakaway valves)
5
•
Moist (wet) compressed air
2
•
Dirty (contaminated with solid particles) compressed air
2
3
When does a fault occur?
•
Regularly (reproducible)
1
2
3
4
•
Sporadically (not reproducible)
5
•
Mostly after a specific operation time
2
3
5
See also
Behavior in case of faults (Page 112)
12.4.2
Remedial measures table 1
Fault profile (symptoms)
Possible cause(s)
Remedial measures
•
Positioner remains in "RUN 1".
•
Initialization started from the end
position and
•
The response time of a maximum of
1 minute was not observed.
•
Network pressure not connected or
it is too low.
•
A waiting time of up to 1 minute is
essential.
•
Do not start initialization from the
end position.
•
Provide the network pressure.
•
Positioner remains in "RUN 2".
•
Transmission ratio selector and
parameter 2
•
"YAGL" and the real stroke do not
match.
•
Incorrectly set stroke on the lever.
•
Piezo valve does not activate.
•
Check settings: see leaflet: "Device
view (7)" picture as well as
parameters 2 and 3
•
Check the stroke setting on the
lever. See table 2
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......