3.2 Structure
SIPART PS2 with PROFIBUS communication
20
Operating Instructions, 09/2007, A5E00127926-07
Figure 3-4
Positioner in flameproof enclosure attached to part-turn actuator
①
Part-turn actuator
②
Dual-action positioner in flameproof enclosure.
③
Pressure gauge block, dual-action.
3.2.2
Type plate structure
IP66
NEMA Type 4x
Made in France
TÜV 00 ATEX 1654
p = 1,4 ... 7bar
0044
F-Nr. N1-P2 -12 3456789
F-Nr. N1-P2 -12 3456789
Ta = -30 ... 50(T6)/65(T5)/80(T4) °C
Install per Contr. Dwg. A5E00065622AA
CL I, DIV 2, GP ABCD T6/T5/T4
CL I, ZN 2, GP IIC T6/T5/T4
(IS) CL I, DIV 1, GP ABCD T6/T5/T4
(FM)/(CSA) CL I, ZN 1, AEx ib IIC / Ex ib IIC T6/T5/T4
$33529('
$33529('
FISCO
device
IECEx TUN 04.0018
Ex ia/ib IIC T6..T1
Technical data and temperature classes see certificate
SIPART PS2 PA Positioner
6DR5510-0EG00-0AA0
II 2 G EEx ia/ib II C T6/T5/T4
Ta = -30 ... 50/65/80°C
Uh= 9 ... 24V
Siemens AG, D-76181 Karlsruhe
www.siemens.com/sipartps2
)0
Type plate structure, example of the EEx ia/ib degree of protection
①
Manufacturer
⑥
Serial number
②
Product name
⑦
Approvals
③
Order number
⑧
Degree of protection
④
Technical data
⑨
Follow the operating instructions
⑤
Place of manufacture
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......