Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
216
Operating Instructions, 09/2007, A5E00127926-07
Effect of the event
1)
5
70
Limit 1 for position
average exceeded
Good, maintenance
requirement
DIA_MAINTENANCE
M1, P
6
71
Limit 2 for position
average exceeded
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12, P
7
72
Limit 3 for position
average exceeded
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M, P
0
73
PST reference time
exceeded (limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
1
74
PST reference time
exceeded (limit 2)
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
2
75
PST reference time
exceeded (limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
3
76 ...
80
Reserved
-
-
-
0
81
Permissible device
temperature exceeded
(limit 1)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M1, P
1
82
Permissible device
temperature exceeded
(limit 2)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M12, P
2
83
Permissible device
temperature exceeded
(limit 3)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M, P
3
84
Permissible device
temperature undershot
(limit 1)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M1, P
4
85
Permissible device
temperature undershot
(limit 2)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M12, P
5
86
Permissible device
temperature undershot
(limit 3)
Uncertain, process
fault, no maintenance
required
DIA_INV_PRO_COND
M, P
6
87
Limit for dead zone
monitoring exceeded
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
4
88 ...
96
Reserved
-
-
-
1)
Effects of the event can be set using the DIAG_EVENT_SWITCH or DIAG_EVENT_SWITCH_2 parameters (default
settings in this case)
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......