Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
215
DIAGNOSTICS_EXTENSION_2 physical block parameter
Effect of the event
1)
Byt
e
Bit No.
Diagnostics events
Quality status code
DIAGNOSTICS bit
Group
0
49
General control valve
fault (limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
1
50
General control valve
fault (limit 2)
Good, maintenance
requirement
DIA_MAINTENANCE_DEMAND
ED
M12
2
51
General control valve
fault (limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
3
52
Pneumatic leakage
(limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
4
53
Pneumatic leakage
(limit 2)
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
5
54
Pneumatic leakage
(limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
6
55
Static friction (limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
0
7
56
Static friction (limit 2)
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
0
57
Static friction (limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
1
58
Lower end stop
monitoring (limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
2
59
Lower end stop
monitoring (limit 2)
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
3
60
Lower end stop
monitoring (limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
4
61
Upper end stop
monitoring (limit 1)
Good, maintenance
requirement
DIA_MAINTENANCE
M1
5
62
Upper end stop
monitoring (limit 2)
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
6
63
Upper end stop
monitoring (limit 3)
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
1
7
64
Limit 1 for path integral
(100% strokes)
exceeded
Good, maintenance
requirement
DIA_MAINTENANCE
M1
0
65
Limit 2 for path integral
(100% strokes)
exceeded
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
1
66
Limit 3 for path integral
(100% strokes)
exceeded
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
2
67
Limit 1 for changes in
direction exceeded
Good, maintenance
requirement
DIA_MAINTENANCE
M1
3
68
Limit 2 for changes of
direction exceeded
Good, maintenance
demand
DIA_MAINTENANCE_DEMAND
ED
M12
2
4
69
Limit 3 for changes of
direction exceeded
Uncertain, maintenance
demand
DIA_MAINTENANCE_ALARM
M
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......