Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
172
Operating Instructions, 09/2007, A5E00127926-07
10.2.3.10
Description of parameter L
L. STRK - monitoring the path integral
Use this parameter to monitor the entire path covered by the final controlling element
continuously.
Configure the following settings to activate the test:
1.
Set the "L. STRK" parameter to "On". Sub-parameters to set the test parameters are
displayed. The test is activated.
2.
Set the suitable parameter values in sub-parameters. The setting options available in
sub-parameters are described below.
The following is applicable for the version with PROFIBUS communication: This test
determines the actuator movements in 100% strokes. In this case, a 100% stroke is equal to
twice the complete path, e.g. from ON→OFF and OFF→ON.
The following is applicable for the standard version and the version with
FOUNDATION fieldbus communication: This test determines the actuator movements in
100% strokes. In this case, a 100% stroke is equal to the complete path, e.g. from ON→OFF
or OFF→ON.
The current value is displayed in the "1 STRKS" diagnostics parameter. The positioner
triggers a fault message if the current value exceeds a limit threshold.
The factory setting is "OFF".
L1.LIMIT - limit for the number of strokes
Use this sub-parameter to set the base limit for the number of strokes. Set the base limit in a
range from "1" to "1.00E8".
The factory setting is "1.00E6".
L2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L2.FACT1".
The threshold 1 fault message is displayed when the limit threshold 1 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.0".
L3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L3.FACT2".
The threshold 2 fault message is displayed when the limit threshold 2 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "2.0".
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......