Commissioning
9.4 Commissioning the part-turn actuators
SIPART PS2 with PROFIBUS communication
130
Operating Instructions, 09/2007, A5E00127926-07
5.
Start the initialization process. Keep the button pressed for more than 5 s until the
following is shown on the digital display:
Note
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN1" to "RUN5" are shown in the
lower line on the digital display. The initialization process depends on the actuator used,
and takes up to 15 minutes.
6.
The following display indicates that the automatic initialization is complete. The total
angle of rotation of the actuator is shown on the upper line on the digital display:
Aborting the automatic initialization process
1.
Press the operating mode button. The following is shown on the digital display:
2.
Exit the Configuration mode. Keep the operating modes button pressed for more than
5 s.
3.
The software status is displayed.
4.
After releasing the operating mode button, the positioner is in the "P manual mode",
i.e. the part-turn actuator has not been initialized.
9.4.3
Manual initialization of part-turn actuators
You can use this function to initialize the positioner without needing to move the actuator to
the end stops. The start and end positions of the actuator travel are set manually. When the
control parameters are optimized, the further initialization process runs automatically.
Conditions
The following conditions must be fulfilled before activating the manual initialization:
1.
The positioner has been prepared for using on linear actuators.
2.
The actuator can be moved completely.
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......