Commissioning
9.4 Commissioning the part-turn actuators
SIPART PS2 with PROFIBUS communication
132
Operating Instructions, 09/2007, A5E00127926-07
7.
Determine the end position 1 of the actuator.
8.
Move the actuator spindle to the desired position by pressing the increment or
decrement buttons.
9.
Accept the current position by pressing the operating mode button. The following is
shown on the digital display:
Note
RANGE fault message
•
The selected end position is beyond the permissible measuring range if the "RANGE"
message appears on the digital display. Correct the settings as follows: Move the
friction clutch until the digital display shows "OK". Press the operating mode button
again.
•
Move the actuator spindle to another position using the increment or decrement
buttons.
•
Abort the manual initialization process by pressing the operating mode button.
Switch to the "P manual mode" and adjust the actuator travel and the position
displacement sensor.
10.
Determine the end position 2 of the actuator.
11.
Move the actuator spindle to the desired position by pressing the increment or
decrement buttons.
12.
Accept the current position by pressing the operating mode button.
13.
The initialization process is automatically resumed. Displays for the initialization steps
from "RUN1" to "RUN5" are shown in the lower line on the digital display.
14.
The following display indicates that the initialization has been completed successfully:
Aborting the manual initialization process
1.
Press the operating mode button. The digital display shows the "INITM" parameter.
The positioner is in the "Configuration" mode.
2.
Exit the "Configuration" mode. Keep the operating modes button pressed for more
than 5 s.
3.
The software status is displayed.
4.
After releasing the operating mode button, the positioner is in the "P manual mode",
i.e. the positioner has not been initialized.
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...