Alarm, fault and system messages
12.2 Diagnostics
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
223
12.2
Diagnostics
12.2.1
Display of diagnostics values
You can access the diagnostics display from the automatic or manual mode by pressing all
three buttons simultaneously for at least two seconds.
The following table provides an overview of values that can be displayed. The third column
contains the German meaning and the corresponding English term used to derive the
abbreviation if it is not self-explanatory.
The diagnostics display has similar structure to that of the "Configuration" mode: The upper
line shown the value of the diagnostics variable and the lower line shows the number and the
abbreviation of the displayed variable.
Use the operating mode button to select the respective next diagnostics value. In order to
select the diagnostics values in the reverse order, keep the operating mode button pressed
and press the decrement button as well.
Specific values can be set to zero by pressing the increment button for at least five
seconds. This is mentioned in the last column of the table.
Some diagnostics value can be greater than 99999. In such a case, the display switches
over to the exponential view. Example: 1234567 is displayed as 1.23E6.
12.2.2
Overview of diagnostics values
Explanation about the table
The following table provides an overview of values that can be displayed. The third column
contains the German meaning and the corresponding English term used to derive the
abbreviation if it is not self-explanatory. The last column contains "X" if the value can be set
to zero.
Overview of diagnostics values
No.
Abbreviation Meaning
Values that can
be displayed
Unit
Reset
possibl
e
1
STRKS
Stroke number (Strokes)
0 ... 4.29E9
-
X
2
CHDIR
Changes of direction (Changes of Direction)
0 ... 4.29E9
-
X
3
CNT
Number of fault messages ( Counter)
0 ... 4.29E9
-
X
4
A1CNT
Number of alarms 1 (Alarm 1 Counter)
0 ... 4.29E9
-
X
5
A2CNT
Number of alarms 2 (Alarm 2 Counter)
0 ... 4.29E9
-
X
6
HOURS
Operating hours (Hours)
0 ... 4.29E9
Hours
-
7
WAY
Determined actuator travel (Way)
0 ... 130
mm or °
-
8
TUP
Actuating time up (Travel Time Up)
0 ... 1000
s
-
9
TDOWN
Actuating time down (Travel Time Down)
0 ... 1000
s
-
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......