SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
217
Alarm, fault and system messages
12
12.1
Representation of system messages on the digital display
12.1.1
System messages before initialization
Remarks about the tables:
nn
stands for variable numeric values
Error symbol
/
(Slash): texts to the left and the right of the slash blink alternately
Messages before initialization (first commissioning)
Line
Message
Up
Down
Meaning / cause
Measure
CPUStart X
X
Message after connecting the electrical
auxiliary power supply
•
Wait
Pnnn.n
X
Potentiometer voltage of a non-initialized
positioner (P-manual mode) (actual position
value in % of the measuring range)
•
Check whether the entire actuator travel
can be covered using the "+" and "-"
buttons and "P---" is never displayed
•
Execute the initialization process
P---
X
Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
•
Switch the transmission ratio selector to
90° especially in case of part-turn
actuators
•
Adjust the effective lever length of linear
actuators as per the measuring range
NOINI
X
Positioner is not initialized
•
Start the initialization process
See also
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......