Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
164
Operating Instructions, 09/2007, A5E00127926-07
C1.LIMIT - limit of the leakage indicator
Use this sub-parameter to set the limit of the leakage indicator in percent. Set the limit in a
range from "0.1" to "100.0". There is no leakage if the limit is less than "30.0".
Utilize the complete sensitivity of the leakage detection as follows:
1.
After initializing the positioner automatically, use a calibration device to initiate a ramp
movement.
2.
Conditions for the ramp movement:
–
The ramp must cover the normal operating range of the valve.
–
The steepness of the ramp must match the dynamic requirements of the
corresponding application.
3.
During the ramp movement, the "15 ONLK" diagnostics parameter provides information
about the actual values. Define the limit of the leakage indicator accordingly.
The positioner triggers a fault message if the current value exceeds one of the three
configurable limit thresholds. How to set the three limit thresholds is described below.
The factory setting is "30.0".
C2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C2.FACT1".
The threshold 1 fault message is displayed when the limit threshold 1 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.0".
C3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C3.FACT2".
The threshold 2 fault message is displayed when the limit threshold 2 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.5".
C4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C4.FACT3".
The threshold 3 fault message is displayed when the limit threshold 3 is exceeded. The
process to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "2.0".
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......