Functions/operations using PROFIBUS PA
11.3 Cyclic data transfer
SIPART PS2 with PROFIBUS communication
212
Operating Instructions, 09/2007, A5E00127926-07
DIAGNOSTICS_EXTENSION_2 physical block parameter
Hard-coded effect of a diagnostics event
Byte Bit
No.
Diagnostics events
Quality status code
DIAGNOSTICS bit
0
49
General control valve fault
(limit 1)
Good, maintenance required
DIA_MAINTENANCE
1
50
General control valve fault
(limit 2)
Good, maintenance required
DIA_MAINTENANCE
2
51
General control valve fault
(limit 3)
Good, maintenance required
DIA_MAINTENANCE
3
52
Pneumatic leakage (limit 1)
Good, maintenance required
DIA_MAINTENANCE
4
53
Pneumatic leakage (limit 2)
Good, maintenance required
DIA_MAINTENANCE
5
54
Pneumatic leakage (limit 3)
Good, maintenance required
DIA_MAINTENANCE
6
55
Static friction (limit 1)
Good, maintenance required
DIA_MAINTENANCE
0
7
56
Static friction (limit 2)
Good, maintenance required
DIA_MAINTENANCE
0
57
Static friction (limit 3)
Good, maintenance required
DIA_MAINTENANCE
1
58
Lower end stop monitoring
(limit 1)
Good, maintenance required
DIA_ZERO_ERR
2
59
Lower end stop monitoring
(limit 2)
Good, maintenance required
DIA_ZERO_ERR
3
60
Lower end stop monitoring
(limit 3)
Good, maintenance required
DIA_ZERO_ERR
4
61
Upper end stop monitoring
(limit 1)
Good, maintenance required
DIA_ZERO_ERR
5
62
Upper end stop monitoring
(limit 2)
Good, maintenance required
DIA_MAINTENANCE
6
63
Upper end stop monitoring
(limit 3)
Good, maintenance required
DIA_MAINTENANCE
1
7
64
Limit 1 for path integral (100%
strokes) exceeded
Good, maintenance required
DIA_MAINTENANCE
0
65
Limit 2 for path integral (100%
strokes) exceeded
Good, maintenance required
DIA_MAINTENANCE
1
66
Limit 3 for path integral (100%
strokes) exceeded
Good, maintenance required
DIA_MAINTENANCE
2
67
Limit 1 for changes of direction
exceeded
Good, maintenance required
DIA_MAINTENANCE
3
68
Limit 2 for changes of direction
exceeded
Good, maintenance required
DIA_MAINTENANCE
4
69
Limit 3 for changes of direction
exceeded
Good, maintenance required
DIA_MAINTENANCE
5
70
Limit 1 for position average
exceeded
Good, maintenance required
DIA_MAINTENANCE
6
71
Limit 2 for position average
exceeded
Good, maintenance required
DIA_MAINTENANCE
2
7
72
Limit 3 for position average
exceeded
Good, maintenance required
DIA_MAINTENANCE
3
0
73
PST reference time exceeded
(limit 1)
Good, maintenance required
DIA_MAINTENANCE
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......