Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
169
The factory setting is "OFF".
G1.LEVL1 - threshold 1
Use this sub-parameter to set a threshold in percent. Use threshold 1 to monitor the upper
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the upper hard end stop
and the initialization value exceeds threshold 1. The process to activate and display this fault
message is described in the "XDIAG" parameter.
The factory setting is "1.0".
G2.LEVL2 - threshold 2
Use this sub-parameter to set a threshold in percent. Use threshold 2 to monitor the upper
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the upper hard end stop
and the initialization value exceeds threshold 2. The process to activate and display this fault
message is described in the "XDIAG" parameter.
The factory setting is "2.0".
G3.LEVL3 - threshold 3
Use this sub-parameter to set a threshold in percent. Use threshold 3 to monitor the upper
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the upper hard end stop
and the initialization value exceeds threshold 3. The process to activate and display this fault
message is described in the "XDIAG" parameter.
The factory setting is "4.0".
10.2.3.8
Description of parameter H
H. TMIN - monitoring the lower limit temperature
Use this parameter to activate the test to continuously monitor the lower limit temperature
inside the enclosure. The current temperature in the enclosure is recorded by a sensor on
the electronic printed circuit board. The limit temperature is monitored in three stages.
Configure the following settings to activate the test:
1.
Set the "H. TMIN" parameter to "On". Sub-parameters to set the test parameters are
displayed. The test is activated.
2.
Set the suitable parameter values in sub-parameters. The setting options available in
sub-parameters are described below.
The positioner triggers a fault message if the lower limit temperature undershoots a
threshold during the test.
The factory setting is "OFF".
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......