Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
173
L4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L4.FACT3".
The threshold 3 fault message is displayed when the limit threshold 3 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "5.0".
10.2.3.11
Description of parameter O
O. DCHG - monitoring the change of direction
Use this parameter to continuously monitor the number of changes of direction of the
actuator caused in the dead zone.
Configure the following settings to activate the test:
1.
Set the "O. DCHG" parameter to "On". Sub-parameters to set the test parameters are
displayed. The test is activated.
2.
Set the suitable parameter values in sub-parameters. The setting options available in
sub-parameters are described below.
The current value is displayed in the "2 CHDIR" diagnostics parameter. The positioner
triggers a fault message if the current value exceeds a limit threshold.
The factory setting is "OFF".
O1.LIMIT - limit for the change of direction
Use this sub-parameter to set the base limit for the number of changes of direction of the
actuator. Set the base limit in a range from "1" to "1.00E8".
The factory setting is "1.00E6".
O2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O2.FACT1".
The threshold 1 fault message is displayed when the limit threshold 1 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.0".
O3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O3.FACT2".
The threshold 2 fault message is displayed when the limit threshold 2 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......