Parameter assignment/Addressing
10.2 Description of parameters
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
157
Figure 10-4 Display of a threshold 3 fault message
The factory setting is "OFF".
See also
Description of parameter A (Page 159)
XDIAG parameter (Page 231)
10.2.2.19
Description of parameter 49
49.FSTY - safety position
Use this parameter to move the actuator to a defined safety position when communication
fails. Three settings are available:
●
FSVL:
the actuator is controlled using the parameterized safety setpoint. This value also
becomes effective after a power failure.
●
FSSP:
the actuator is controlled using the last effective setpoint.
●
FSAC:
the exhaust air valve is opened. The single-acting actuator moves to the end position due
to its spring force.
The factory setting is "FSAC".
10.2.2.20
Description of parameter 50
50.FSTI - monitoring time to set the safety position
If communication fails, the positioner switches to the safety position after the set value
expires.
The factory setting is "0".
Содержание SIPART PS2 PA 6DR55 Series
Страница 2: ......
Страница 270: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 270 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 271: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions 09 2007 A5E00127926 07 271 ...
Страница 272: ...Appendix A 3 Test report SIPART PS2 with PROFIBUS communication 272 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 286: ...Glossary SIPART PS2 with PROFIBUS communication 286 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 290: ...Index SIPART PS2 with PROFIBUS communication 290 Operating Instructions 09 2007 A5E00127926 07 ...
Страница 291: ......