Installation
4.2 Electrical Installation
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
71
Default setting 25: "Distributed conveyor systems with fieldbus, safety"
DO 0: p0730, DO 1: p0731
DI 0: r0722.0, …, DI 5: r0722.5
p2081[0] = r0722.0, …, p2081[3] = r0722.3
p0730 = r2094.0, p0731 = r2094.1
Speed setpoint (main setpoint): p1070[0] = 2050[1]
4.2.17
Fail-safe digital input
To enable a safety function via the terminal strip of the inverter, you need a fail-safe digital
input.
For specific default settings of the terminal strip, e.g. default
setting 2, the inverter combines two digital inputs to form one
fail-safe digital input FDI 0.
Which devices are you allowed to connect?
The fail-safe digital input is designed for the following devices:
●
Connection of safety sensors, e.g. emergency stop command devices or light curtains.
●
Connection of pre-processing devices, e.g. fail-safe control systems and safety relays.
Signal state
The inverter expects signals with the same state at its fail-safe digital input:
●
High signal: The safety function is deselected.
●
Low signal: The safety function is selected.