Advanced commissioning
6.12 Setpoints
Converter with the control units CU240D-2
170
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Parameter
Table 6- 17 Basic setup of motorized potentiometer
Parameter
Description
Setting
p1035[0…n]
BI: Motorized potentiometer
setpoint higher
Signal source to continuously increase the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.13
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1036[0…n]
BI: Motorized potentiometer
setpoint lower
Signal source to continuously decrease the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.14
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
p1040[0…n]
Motorized potentiometer
start value [rpm]
Start value that is effective when the motor is switched on.
Factory setting: 0 rpm
p1047
MOP ramp-up time [s]
MOP ramp-up time
Factory setting: 10 s
p1048
MOP ramp-down time [s]
MOP ramp-down time:
Factory setting: 10 s
r1050
Motorized potentiometer,
setpoint after the ramp-
function generator
Motorized potentiometer, setpoint after the ramp-function generator
p1070[0…n]
CI: Main setpoint
Signal source for the main setpoint
The factory setting depends on the Control Unit.
With PROFIBUS or PROFINET interface: [0] 2050[1]
Without PROFIBUS or PROFINET interface: [0] 755[0]
p1071[0…n]
CI: Main setpoint scaling
Signal source for scaling the main setpoint
Factory setting: 1
r1073
CO: Main setpoint active
Displays the active main setpoint
p1075[0…n]
CI: Supplementary setpoint
Signal source for the supplementary setpoint
Factory setting: 0
p1076[0…n]
CI: Supplementary setpoint
scaling
Signal source for scaling the supplementary setpoint
Factory setting: 0