Backing up data and series commissioning
7.2 Backup the settings to a PC
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
251
Procedure with Startdrive when the safety functions are enabled
1.
Save the project.
2.
Select "Load to device".
3.
Connect Startdrive online with the drive.
4.
Press the "Start safety commissioning" button.
5.
Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6.
Press the "End safety commissioning" button.
7.
Confirm the prompt for saving your settings (copy RAM to ROM).
8.
Disconnect the online connection.
9.
Switch off the inverter power supply.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter power supply again.
You have transferred the settings from the PG to the inverter with Startdrive and have
activated the safety functions.
❒