Advanced commissioning
6.4 Drive control via PROFIBUS or PROFINET
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
125
No.
Description
86 hex
Write access only for commissioning (p0010 = 15) (operating state of the inverter prevents
a parameter change)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within
the "absolute" limits, but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for
the inverter power)
CC hex Change request not permitted (change is not permitted as the access code is not availa-
ble)
PNU (parameter number) and page index
The parameter number is located in value PNU in the 1st word of the parameter channel
(PKE).
The page index is located in the 2nd word of the parameter channel (IND bit 7 … 0).
Parameter number
PNU
Page index
0000 … 1999
0000 … 1999
0 hex
2000 … 3999
0000 … 1999
80 hex
6000 … 7999
0000 … 1999
90 hex
8000 … 9999
0000 … 1999
20 hex
10000 … 11999
0000 … 1999
A0 hex
20000 … 21999
0000 … 1999
50 hex
30000 … 31999
0000 … 1999
F0 hex
60000 … 61999
0000 … 1999
74 hex
Subindex
For indexed parameters, the parameter index is located in subindex (IND Bit 15 … 8) as
hexadecimal value.