Advanced commissioning
6.7 Switching over the drive control (command data set)
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
139
An overview of all the parameters that belong to the command data sets is provided in the
List Manual.
Note
The converter requires approx. 4 ms to switch over the command data set.
Changing the number of command data sets
Procedure
1.
Set p0010 = 15.
2.
The number of command data sets is configured with p0170.
3.
Set p0010 = 0.
You have changed the number of command data sets.
❒
Copying command data sets
Procedure
1.
Set p0809[0] to the number of the command data set whose settings you wish to copy
(source).
2.
Set p0809[1] to the number of the command data set in which you wish to copy the
settings.
3.
Set p0809[2] = 1
4.
The inverter sets p0809[2] = 0.
You have copied the settings of a command data set into another command data set.
❒
Parameter
Parameter
Description
p0010
Drive commissioning parameter filter
r0050
Command data set CDS active
Displays the number of the currently active command data set
p0170
Number of command data sets (CDS) (factory setting: 2)
p0170 = 2, 3 or 4
p0809[0]
Copying the command data set CDS (factory setting: 0)
[0] Source command data set
[1] Target command data set
[2] 0→1: Starts the copy operation