Alarms, faults and system messages
8.6 List of alarms and faults
Converter with the control units CU240D-2
280
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Number Cause
Remedy
A07850
A07851
A07852
External alarm 1 … 3
The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for
the external alarm 1… 3.
Remedy: Remove the causes of these alarms.
F07860
F07861
F07862
External fault 1 … 3
Remove the external causes for this fault.
F07900
Motor blocked
Check that the motor can run freely.
Check the torque limits (r1538 and r1539).
Check the parameters of the "Motor blocked" message (p2175, p2177).
F07901
Motor overspeed
Activate precontrol of the speed limiting controller (p1401 bit 7 = 1).
Increase hysteresis for overspeed signal p2162.
F07902
Motor stalled
Check whether the motor data has been parameterized correctly and
perform motor identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
A07903
Motor speed deviation
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
A07910
Motor overtemperature
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or PT1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
A07920
Torque/speed too low
The torque deviates from the torque/speed envelope curve.
•
Check the connection between the motor and the load.
•
Adapt the parameterization corresponding to the load.
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
•
Check the connection between the motor and the load.
•
Adapt the parameterization corresponding to the load.
F07924
Torque/speed too high
A07927
DC braking active
Not required
A07980
Rotary measurement activated
Not required
A07981
No enabling for rotary measure-
ment
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
A07991
Motor data identification activated Switch on the motor and identify the motor data.
F08501
Setpoint timeout
•
Check the PROFINET connection.
•
Set the controller to RUN mode.
•
If the error occurs repeatedly, check the set monitoring time p2044.
F08502
Monitoring time sign-of-life expired
•
Check the PROFINET connection.
F08510
Send configuration data not valid
•
Check the PROFINET configuration
A08511
Receive configuration data not
valid
A08526
No cyclic connection
•
Activate the controller with cyclic operation.
•
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).