Installation
4.3 Connecting the inverter to PROFINET
Converter with the control units CU240D-2
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
75
Installing GSDML (Page 76)
Device name
In addition to the MAC address and IP address, PROFINET also uses the device name to
identify PROFINET devices (Device name). The device name must be unique across the
PROFINET network.
To assign the device name, you need an engineering software, e.g. HW-Config or
STARTER.
The inverter saves the device name on the inserted memory card.
IP address
In addition to the device name, PROFINET also uses an IP address.
You have the following options to specify the IP address of the inverter:
●
You specify the IP address via an engineering software, e.g. via HW-Config or
STARTER.
●
The IO Controller assigns an IP address to the inverter.
Telegram
Set the same telegram in the inverter as in the IO Controller. Interconnect the telegrams in
the control program of the IO Controller with the signals of your choosing.
Drive control via PROFIBUS or PROFINET (Page 113)
Application examples
You can find application examples for PROFINET communication on the Internet:
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F
via PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(
https://support.industry.siemens.com/cs/ww/en/view/60441457
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI
(