Advanced commissioning
6.22 Efficiency optimization
Converter with the control units CU240D-2
242
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Table 6- 44 Efficiency optimization, method 1
Parameter
Description
Setting
p1570
Flux setpoint [%]
Factory setting: 100 %
p1580
Efficiency optimization [%]
0 %: Efficiency optimization is deactivated.
100 %: In no-load operation, the inverter reduces the flux setpoint to
50% of the rated motor flux.
The factory setting depends on the inverter.