Installation
4.2 Electrical Installation
Converter with the control units CU240D-2
58
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Knorrtec (
http://www.knorrtec.de/index.php/en/company-profile/siemens-solution-
Table 4- 12 Push-Pull variant PROFINET and 24 V DC connectors
Connector
Article number
24 V DC power supply
6GK1907-0AB10-6AA0
RJ45 PROFINET
6GK1901-1BB10-6AA0
Table 4- 13 Fibre optic connectors
Connector
Article number
IE SC RJ POF PLUG PRO
6GK1900-0MB00-6AA0
IE SC RJ PCF PLUG PRO
6GK1900-0NB00-6AA0
Table 4- 14 Mains connector
Power rating
cable size
Article number
0.75 kW … 1.50 kW
2.5 mm
2
(14 AWG)
3RK1911-2BE50
3.00 kW … 4.00 kW
4 mm
2
(12 or 10 AWG)
3RK1911-2BE10
5.50 kW … 7.50 kW
6 mm
2
(10 AWG)
3RK1911-2BE30
You find information about motor connectors in the internet:
Solution partner
https://www.automation.siemens.com/solutionpartner/partnerfinder/Partner-
Cable lengths
Table 4- 15 Maximum cable lengths
Cable
Screening
Max. length
Motor
1)
Screened
15 m (49 ft)
Unscreened
30 m (98 ft)
Temperature sensor
1)
Screened
15 m (49 ft)
Unscreened
30 m (98 ft)
Motor holding brake
1)
Screened
15 m (49 ft)
Unscreened
30 m (98 ft)
Digital inputs
Screened
30 m (98 ft)
Digital outputs
Screened
30 m (98 ft)