Advanced commissioning
6.11 Safe Torque Off (STO) safety function
Converter with the control units CU240D-2
160
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Procedure
1.
Press the "End safety commissioning" button.
2.
Confirm the prompt for saving your settings (copy RAM to ROM).
3.
Disconnect the online connection.
4.
Select the "Load from device (software)" button.
5.
Save the project.
6.
Switch off the inverter power supply.
7.
Wait until all LEDs on the inverter go dark (no voltage condition).
8.
Switch the inverter power supply on again.
Your settings are now active.
❒
Parameter
Description
p9700 = D0 hex
SI copy function (factory setting: 0)
Start the SI parameter copy function.
p9701 = DC hex
Confirm data change (factory setting: 0)
Confirm SI Basic parameter change
p0010 = 0
Drive commissioning parameter filter
0: Ready
p0971 = 1
Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then
p0971 = 0.
Checking the interconnection of digital inputs
The simultaneous connection of digital inputs with a safety function and a "standard" function
may lead to the drive behaving in unexpected ways.