Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Converter with the control units CU240D-2
108
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
6.3.1
Digital inputs
Changing the function of a digital input
Interconnect the status parameter of the digital input with a
binector input of your choice.
Binector inputs are marked with "BI" in the parameter list of
the List Manual.
Table 6- 3
Binector inputs (BI) of the inverter (selection)
BI
Significance
BI
Significance
p0810 Command data set selection CDS bit 0
p1036 Motorized potentiometer, setpoint, lower
p0840 ON/OFF1
p1055 Jog bit 0
p0844 OFF2
p1056 Jog bit 1
p0848 OFF3
p1113 Setpoint inversion
p0852 Enable operation
p1201 Flying restart enable signal source
p0855 Unconditionally release holding brake
p2103 1. Acknowledge faults
p0856 Enable speed controller
p2106 External fault 1
p0858 Unconditionally close holding brake
p2112 External alarm 1
p1020 Fixed speed setpoint selection bit 0
p2200 Technology controller enable
p1021 Fixed speed setpoint selection bit 1
p3330 Two-wire/three-wire control, control
command 1
p1022 Fixed speed setpoint selection bit 2
p3331 Two-wire/three-wire control, control
command 2
p1023 Fixed speed setpoint selection bit 3
p3332 Two-wire/three-wire control, control
command 3
p1035 Motorized potentiometer, setpoint, raise
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital input - example
In order to switch on the motor with digital input DI 2,
you have to connect the status parameter of DI 2 to
p0840: Set p0840 = 722.2.