Advanced commissioning
6.21 Monitoring the driven load
Converter with the control units CU240D-2
234
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
6.21.4
Load monitoring
The load monitoring comprises the following components:
●
Load failure monitoring
●
Monitoring for torque deviation
●
Speed deviation monitoring
If the load monitoring detects load failure, the inverter issues fault F07936. For a torque and
speed deviation, as response, you can either set an alarm or a fault. Details are provided in
the following descriptions.
Settings
Table 6- 42 Setting options for load monitoring
Parameters
Description
p2193
Load monitoring configuration (factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring