Installation
4.2 Electrical Installation
Converter with the control units CU240D-2
64
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Default setting 3: "Conveyor system with 4 fixed frequencies"
DO 0: p0730, DO 1: p0731
DI 0: r0722.0, …, DI 5: r0722.5
Fixed speed setpoint 1: p1001, … fixed speed setpoint 4: p1004, fixed speed setpoint active: r1024
Speed setpoint (main setpoint): p1070[0] = 1024
Several of the DI 0, DI 1, DI 4, and DI 5 = high: the inverter adds the corresponding fixed speed set-
points.
Default setting 4: "Conveyor system with fieldbus"
DO 0: p0730, DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 2050[1]