Analog Electronic Modules
12-36
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Measuring range -- temperature coefficient -- measuring range
The following table shows which temperature coefficients and which measuring
ranges can be configured for the specific measuring type:
Measurement type
Temperature coefficient
Measuring range
disabled
--
--
4-wire resistor
3-wire resistor
--
150
Ω
/ 300
Ω
/ 600
Ω
/ 3000
Ω
2-wire resistor
--
150
Ω
/ 300
Ω
/ 600
Ω
/ 3000
Ω
/
PTC
3-wire thermal resistor
Pt 0.003850/ Pt 0.003916 /
Pt 0.003902 / Pt 0.003920 /
Pt 0.003851
1)
Pt100 climate range /
Pt100 standard range /
Pt200 climate range /
Pt200 standard range /
Pt200 standard range /
Pt500 climate range /
Pt500 standard range /
Pt1000 climate range /
Pt1000 standard range
Ni 0.006180
1)
/ Ni 0.006720
Ni100 climate range /
NI100 standard range /
Ni120 climate range /
Ni120 standard range /
Ni200 climate range /
Ni200 standard range /
Ni500 climate range /
Ni500 standard range /
Ni1000 climate range /
Ni1000 standard range
Ni 0.005000
Ni 1000 climate range
2)
Ni 1000 standard range
2)
Cu 0.00427
1)
Cu10 climate range /
Cu10 standard range
1)
The preceding temperature coefficient are applicable for Europe.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...