Interface Modules
8-4
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for the IM151-3 PN interface module
Table 8-5
Parameters for the IM151-3 PN interface module
IM151-3 PN
Value range
Default
setting
Effective range
Bus length
≤
1 m / > 1 m
≤
1 m
ET 200S
Interference Frequency
Suppression
50 Hz/60 Hz
50 Hz
ET 200S
Reference junction slot
None/2 to 63
none
ET 200S
Reference junction input
RTD on channel 0/
RTD on channel 1
0
ET 200S
DP interrupt mode (only with IM151-1 STANDARD (from 6ES7 151-1AA04-0AB0),
IM151-1 FO STANDARD (from 6ES7 151-1AB03-0AB0)
and IM151-1 HIGH FEATURE)
This parameter allows you to enable or disable DPV1 operation of the ET 200S. If
DPV1 mode is enabled, data sets and interrupts are supported via class 1 services
and class 2 services (configurable).
Requirements:
•
The DP master also support DPV1.
Bus length
≤
1 m: default, the maximum bus length is 1 m.
>
1 m: the bus length of the ET 200S is
>
1 m and can be a maximum 2 m. This
setting will, however, increase the response time of the ET 200S (see Appendix D).
Operation at Preset <> Actual configuration
If the parameter is enabled and:
•
Modules are removed and inserted during operation, this does not lead to a
station failure of the ET 200S.
•
The actual configuration differs from the expected configuration, the ET 200S
continues to exchange data with the DP master.
If the parameter is disabled and:
•
Modules are removed and inserted during operation, this leads to a station
failure of the ET 200S.
•
The actual configuration differs from the expected configuration, there is no
data transfer between the DP master and the ET 200S. Exception: option
handling with RESERVE modules (see Chapter 3.8).
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...