Interface Modules
8-2
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for the IM151-1 STANDARD and IM151-1 FO STANDARD interface
modules
Table 8-2
Parameters for the IM151-1 STANDARD and IM151-1 FO STANDARD interface
modules
IM151-1 STANDARD/IM151-1
FO STANDARD
Value range
Default
4)
Applicability
DP interrupt mode
DPV0/DPV1
DPV0
ET 200S
Bus length
≤
1 m / > 1 m
≤
1 m
ET 200S
Operation with Set and <>
Actual Configuration
1)
Disable/enable
Disable
ET 200S
Diagnostic interrupt
3)
Disable/enable
disable
ET 200S
Process interrupt
3)
Disable/enable
disable
ET 200S
Insert/Remove module
interrupt
2) 3)
Disable/enable
disable
ET 200S
Module diagnosis
Disable/enable
enabled
ET 200S
Module status
Disable/enable
enabled
ET 200S
Channel-specific diagnostics
Disable/enable
enabled
ET 200S
Option handling, general
Disable/enable
disable
ET 200S
Option handling: Slots 2 to 63
Disable/enable
disable
Module
Analog-value format
SIMATIC S7/
SIMATIC S5
S7
ET 200S
Interference Frequency
Suppression
50 Hz/60 Hz
50 Hz
ET 200S
Reference junction slot
None/2 to 63
none
ET 200S
Reference junction input
RTD on channel 0/
RTD on channel 1
0
ET 200S
1)
Note also the option handling parameters (see Chapter 3.8).
2)
In the device database file, the default setting of the parameter is ”Disable”.
3)
Only configurable in DPV1 mode.
4)
The default settings are applicable for the default startup (if no other parameters are specified
by the DP master).
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...