Power modules
10-14
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Technical data
Dimensions and weight
Dimensions
W x H x D (mm)
Weight
15 x 81 x 52
34g
Voltages, currents, electrical potentials
Rated load voltage
24--56.7 VDC
24--48 VAC/
120 V/230 VAC
•
Overvoltage protection
Yes
Max. current capacity
10A
•
for 24--56.7 VDC
to 30
°
C: max. 10A
(164 ft)
to 40
°
C: max. 9A
(164 ft)
to 60
°
C: max. 7A
(164 ft)
•
for 24--48/120/230 VAC
to 30
°
C: max. 8A
(164 ft)
to 40
°
C: max. 7A
(164 ft)
to 60
°
C: max. 5A
(164 ft)
•
Short-circuit protection
yes, IEC 127-2/1,
250 V, 10 A,
fast-acting fuse
(5 x 20 mm),
replaceable
1)
Electrical isolation
•
Between rated load
voltage and backplane
bus
Yes
•
Between the
power modules
Yes
Insulation tested with
1500 VAC
Current consumption
From the backplane bus
max. 9.5mA (164 ft)
•
From load voltage L1/L+
(without load)
max. 9mA (164 ft)
Power loss of the module
Max. 5W
Status, alarms, diagnostics
Diagnostics function
Yes
•
Group error
•
Rated load voltage
monitoring
red LED ”SF”
Green LED ”PWR”
•
Fuses
Green LED ”FSG”
•
Reading of diagnostic
data
Yes
1)
The fuses on this module are only auxiliary
fuses; external overcurrent protection (suitable
for branch circuits depending on the local
electrotechnical regulations) is required in the
power supply cables of the load current circuit.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...