Installation
4-12
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Installing the shield contact
1. Push the shield contact element onto the first terminal module from below.
2. Push the shield contact element onto the last terminal module from below.
In order to achieve stability of the conductor rail between two shield contact
elements during installation, you must connect an additional shield contact
element after every sixth terminal module (given a width of 15 mm).
3. Saw off the correct length from the conductor rail. The length of the rail is: the
distance between the shield c 45 mm.
4. Push the conductor rail into the shield contact element. After installation, the
conductor rail must protrude from the shield contact element by 15 mm
on the left or right.
5. Attach the shield terminals on the conductor rail (between the shield
contact elements).
6. Attach the ground connection terminal to the protruding conductor rail.
Shield contact elements
Shield terminals
Conductor rail
Ground connection terminal
Figure 4-7
Installing the shield contact
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...