Brief Instructions on Commissioning ET 200S
2-3
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Prerequisites
•
You must have set up an S7 station consisting of a power supply module and a
DP master (for example, CPU 315-2 DP). A CPU 315-2 DP was used as the
DP master in this example. However, any other DP master (IEC 61784-1:2002
Ed1 CP 3/1) could be used instead.
•
STEP 7
(V 5.0 with ServicePack 3 or higher) is fully installed on your
programming device (PG). You must be familiar with STEP 7.
•
The programming device must be connected to the DP master.
Installation
1. Mount the rail (35 mm x 7.5 mm or 15 mm) with a length of at least 210 mm on
a solid base.
2. Install the various modules on the rail beginning on the left (hook on, swing in,
move to the left). Adhere to the following sequence:
-- IM151-1 STANDARD interface module
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- Terminating module
3. Set the PROFIBUS address 3 on the IM 151-1 STANDARD interface module.
64
32
16
8
4
2
1
ON
OFF
PROFIBUS address 3
Figure 2-2
Setting PROFIBUS Address 3
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...