Digital Electronic Modules
11-84
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Technical specifications
Dimensions and weight
Dimensions W x H x D
15 x 81 x 52 (mm)
Weight
Approx. 50 g
Module-specific data
Supports clock
synchronized mode
No
Number of outputs
2
Cable length
•
Unshielded
max. 600 m (164 ft)
•
shielded
max. 1,000 m
(164 ft)
Voltages, currents, electrical potentials
Rated power supply voltage
L+ (from power module)
24 VDC
Reverse polarity protection
current per channel
Yes
•
up to 50
°
C
Max. 5 A
•
to 60
°
C
Max. 4 A
Electrical isolation
•
Between the channels
Yes
•
Between channels and
backplane bus
Yes
•
Between channels and
power supply voltage
Yes
•
Between power supply
voltage and backplane
bus
Yes
Approved potential
difference
•
Between power supply
voltage and backplane
bus
75 VDC, 60 VAC
•
Between channels and
backplane bus
240 VAC
•
Between channels and
power supply voltage
240 VAC
Isolation tested
•
Between power supply
voltage and backplane
bus
500 VDC
•
Between channels and
backplane bus
2500 VDC
•
Between channels and
power supply voltage
2500 VDC
Current consumption
•
From power
supply L+
max. 30 mA
•
From the backplane bus max. 10 mA
Power loss of the module
Typical 0.6 W
Status, interrupts, diagnostics
Status display
Green LEDs pro
Channel
Diagnostic functions
No
Data for Selecting an Actuator
Output current
•
Continuous thermal
current
Max. 5 A
•
Minimum load current
8 mA
Connecting 2 outputs in
parallel
•
For redundant triggering
of a load
No
•
To increase
performance
No
Actuation of a digital input
Yes
Switching frequency
•
with ohmic load
2 Hz
•
with inductive load
0.5 Hz
•
With lamp load
Limitation (internal) of the
inductive disconnection
voltage
Short-circuit protection of
the output
1)
2 Hz
No
No
1)
The relay outputs must be externally fused with
6 A.
When installed in a hazardous zone as per the
National Electric Code (NEC) the fuse must
only be removed with a suitable tool if the
module is not in the explosive zone.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...