Power modules
10-12
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Note
The PM-E 24--48 VDC/24--230 VAC power module (6ES7 138-4CB10-0AB0) is not
a direct replacement for the device with the order number 6ES7 138-4CB00-0AB0
for AC applications, because either AC or DC power supply must be specified. The
new module is a direct replacement with DC applications, because the default for
the new parameter is ”DC”. If you wish to use the 6ES7 138-4CB00-0AB0 device
for AC applications, a new hardware configuration must be set up and the value
”AC” must be specified for the ”Load voltage type” parameter.
If the hardware configuration is not changed for AC applications, the SF status
LED remains on continuously. If the ”Lo load voltage” diagnostic alarm is activated,
multiple interrupts are activated in every AC cycle. However, the electronic
modules connected to the potential group of this PM-E operate normally.
Terminal assignment
The following table shows the terminal assignment of the PM-E 24--48
VDC/24--230 VAC power module for the various terminal modules:
Table 10-4 Terminal assignment of the PM-E 24--48 VDC/24--230 VAC power module
View
Terminal assignment
Remarks
M/N
M/N
AUX1
24--48 VDC/ L1
AUX1
AC
∽
TM-P15S23-A1 and PM-E 24--48 VDC/24--230 VAC
2
3
4
6
7
8
AUX1
24--48 VDC/ L1
24V DC
A
A
4 8
A
A
24--48 VDC/ L1: Rated
load voltage
M/ N: Ground/neutral
conductor
AUX1: can be used as
protective conductor
terminal or any
potential rail up to the
total load voltage.
AC
∽
AUX1
AUX1
TM-P15S23-A0 and PM-E 24--48 VDC/24--230 VAC
2
3
4
6
7
8
AUX1
24--48 VDC/ L1
24--48 VDC/ L1
M/N
M/N
24V DC
A
A
4 8
A
A
24--48 VDC/ L1: Rated
load voltage
M/ N: Ground/neutral
conductor
AUX1: can be used as
protective conductor
terminal or any
potential rail up to the
total load voltage.
AUX1 is used as PE.
Содержание SIMATIC ET 200S
Страница 42: ...Product Overview 1 16 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 64: ...Brief Instructions on Commissioning ET 200S 2 22 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 112: ...Configuration Options 3 48 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 232: ...Commissioning and Diagnostics 6 72 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 244: ...General Technical Specifications 7 12 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 274: ...Interface Modules 8 30 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 538: ...4 IQ SENSE 13 18 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 564: ...Address Space of the Input and Outputs of the ET 200S C 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 574: ...Response Times D 10 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 580: ...Special Measures for Interference Free Operation F 4 ET 200S Distributed I O System EWA 4NEB 780602402 12 ...
Страница 600: ...Product Information on the Use of subassemblies modules in a Zone 2 Hazardous Area 2 A5E00352937 02 ...